SMART I/O User’s Manual
March 12, 1996
©1996 PEP Modular Computers GmbH
Page 5 - 70
Chapter 5 Analog Modules
5.3.8.4 SMADCSetCyclicCalib
Syntax
error_code SMADCSetCyclicCalib(u_int8 PortNr,
u_int secs);
Description
This function sets the time between two calibration cycles in seconds. If
secs=0, then cyclic calibration is disabled.
Input
u_int8 PortNr
Port number of module for calibration
(from 0 to 10)
u_int16 secs
Time in seconds between two calibration
cycles
Output
error_code SUCCESS
E_MNF
If wrong type of module or no module
is fitted on the selected port
or standard OS-9 error code (refer to the OS-9
Technical Manual Error Codes Section).
Example
RetVal = SMADCSetCyclicCalib(0 , 120);
Vue de la page 225